1. Installation:35mm DIN rail
2. Power supply:230VAC 50/60Hz
3. Max.Loading power:1~40A Adjustable(default:40A)
1~63A Adjustable(default:63A)
4. Over-voltage protection value range:230V~300~OFF(default:270V)
Over-voltage recovery voltage range:225V--295V(default:250V)
Over-voltage protection action time:0.1s~30s(default value:0.5s)
Over-voltage recovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:140V--210V --OFF(default:170V)
Under-voltage recovery voltage range:145V--215V (default:190V)
Under-voltage protection action time:0.1s~30s(default:0.5s)
Under-voltage recovery delay time:1s~500s(default:30s)
6.Over-current adjustment range:1-40A (default:20A) 1-63A (default:40A)
Over-current action range:0.1~30 second (default:0.5s)
Over-current recovery delay time:1s~500s(default:30s)
7. Power-on delay time:1s~500s(default:10s)
9. Power consumption: <2W
10. Electric machinery life: 100,000 times
11. Restore factory settings: press the down button for more than 12s
12. Fault inquiry: Press the UP button from more than 12S